Model: Modular Online UPS Power Melody Star Series (3ph in/3ph out)
Modular UPS Quick View
1: Modular UPS with hot swappable Battery Cabinet
2: UPS with < 3% Input THDi
3: UPS Built-in Manual Bypass Switch
4: Modular UPS with 0.8 / 0.9 output Power Factor
Key Features
All the power modules and systems are protected simultaneously by the hardware and the software. All kinds of protection functions are achieved, including current and voltage monitoring, temperature monitoring and short circuit etc… . This smart monitoring enhance reliability and availability as the operator is able to anticipate potential problems prior these occur.
RM series offers a high installation flexibility that reduces installation time. Consequently, it is very easy to maintain and to control each module which provides highest reliability and best protection for supplied load. With the large touch screen LCD panel, the user can easily access to the information of every power module.
Each UPS module is built with a separate 3.2kW charger. With 10 installed modules, the total charging power will equal to 32kW. This charger is controlled by a DSP with intelligent digital arithmetic that enhance battery lifetime.
MS Series 10K-200Kva |
||||
Capacity |
10-200KVA |
|||
Main Input |
||||
Input voltage |
380V/400V/415V(line to line) |
|||
Input frequency |
50/60Hz |
|||
Power factor |
> 0.99 |
|||
Input cuurent THD(Total Harmonic Distortion) |
< 3% |
|||
Input voltage window |
-40%~+25% |
|||
Frequency window |
40-70HZ |
|||
Battery |
||||
Battery voltage |
± 240VDC |
|||
Charger power |
20%*Power |
|||
Charger voltage precision |
1% |
|||
Bypass |
||||
Bypass voltage |
380V/400V/415V, three phase |
|||
Bypass voltage window |
-20%-+15%, full load, settable |
|||
Bypass overload capabiltiy |
150%, long time operation |
|||
180%, shut down after 10 minutes |
||||
> 180%, shut down after 200ms |
||||
Output |
||||
Output voltage |
380V/400V/415V, three phase |
|||
Voltage precision |
± 0.5% (balance load), ± 1% (unbalance load) |
|||
Voltage THD(Total Harmonic Distortion) |
THD< 1%(linear load), THD< 3%(nonlinear load) |
|||
Power factor |
0.8 |
|||
Phase tolerance |
120° ± 0.5° (balance and unalance load) |
|||
Crest factor |
3: 1 |
|||
Overload capabiltiy |
110%, transfer to bypass after 1hour |
|||
125%, transfer to bypass after 10 minutes |
||||
150%, transfer to bypass after 1 minute Related Search
Three Phase Power Supply
Uninterruptible Power Supply
Online Power Supply
Three Phase Energy Meter
Power Energy Saving Lamp
Power Saver Energy Saving
More>>
Find more related products in following catalogs on Hisupplier.comCompany InfoShenzhen UPSEN Electric Co., Ltd [China (Mainland)]
Business Type:Manufacturer You May Like:
Printable Page
Bookmark this page
Sitemap XML About HiSupplier Help Center Customer Service Friend Links Site Map Archives Browse by: China Suppliers - Hot Products - Products Directory - Offers Directory - Suppliers Directory - Buyers Directory Language Option: العربية - Nederlands- Français- Deutsch- Italiano- 日本語- 한국의- Português- Pусский- Español Copyright © HiSupplier.com Online Inc. All Rights Reserved.
|