Place of Origin: | Zhejiang, China (Mainland) |
Add to My Favorites | |
HiSupplier Escrow |
Online Parallel 10KW 20KW 30KW 3 Phase Uninterruptible Power Supply
Model: High Frequency Online UPS View Star Series 10K-30Kva (3ph in/3ph out)
Quick View
1: UPS use for Servers , Data center , Critical network devices , Sensitive electronic equipment , Telecom
2: High Frequency Transformerless Online UPS with 3 Phase with lower noisy
3: UPS with stable output and all types protections
4: UPS with DSP and IGBT Tech
5: N+X parallel redundancy function for UPS
Key Features
1.True double-conversion
2. DSP technology guarantees high performance
3. Output power factor 0.8
3. Wide input voltage range (110-300 VAC)
4. Active power factor correction in all phases
5. 50Hz/60Hz frequency converter mode
6. ECO mode operation for energy saving
7. Accepts dual-mains inputs
8. Emergency power off function (EPO)
9. Generator compatible
10. SNMP+USB+RS-232 multiple communications
11. 3-stage extendable charging design for optimized battery performance
12. Adjustable battery numbers
13. Maintenance bypass available
14. Optional N+X parallel redundancy
15. Optional isolation transformer offers full isolation and complete common mode noise rejection
Technical Specification
VIEW STAR 3P/3P 10K/15K/20K/30K ONLINE UPS SELECTION GUIDE | |||||
MODEL | VS33 10K(L) | VS33 15K(L) | VS33 20K(L) | VS33 30K(L) | |
PHASE | 3 phase in / 3 phase out | ||||
CAPACITY | 10000VA/8000 W | 15000VA/12000W | 20000VA /16000W | 30000VA/24000W | |
INPUT | |||||
Nominal Voltage | 3 x 400 VAC (3Ph+N) | ||||
Voltage Range | 305-478 VAC (3-phase) @ 100% load 190-520 VAC (3-phase) @ 50% load |
||||
Frequency Range | 46~54 Hz or 56~64Hz | ||||
Power Factor | 0.99 @ 100% load | ||||
OUTPUT | |||||
Output Voltage | 3 x 400 VAC (3Ph+N) | ||||
AC Voltage Regulation (Batt. Mode) | ± 1% | ||||
Frequency Range (Synchronized Range) | 46~54Hz or 56~64Hz | ||||
Frequency Range (Batt. Mode) | 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz | ||||
Current Crest Ratio | 3:1 (max.) | ||||
Harmonic Distortion | 2 % THD (Linear Load) 5 % THD (Non-linear Load) | ||||
Transfer Time | AC mode to Battery mode | zero | |||
Inverter to Bypass | zero | ||||
Waveform (Batt. Mode) | Pure Sine Wave | ||||
EFFICIENCY | |||||
AC Mode | 89% | 89% | 89% | 90% | |
Battery Mode | 86% | 88% | 87% | 89% | |
BATTERY | |||||
Standard Model | Battery Type | 12 V / 9 AH | |||
Numbers | 20 pcs (18 - 20 adjustable) | 20 pcs (18 - 20 adjustable)x 2 strings | 20pcs (18-20adjustable) x 3 strings | ||
Typical Recharge Time | 9 hours recover to 90% capacity | ||||
Charging Current (max.) | 1A | 2A | 2A | 4A | |
Charging Voltage | 273 VDC ± 1%(based on 20 pcs batteries) |