Place of Origin: | Zhejiang, China (Mainland) |
Add to My Favorites | |
HiSupplier Escrow |
High Frequency Pure Sine Wave 380V / 400V / 415VAC Modular UPS Power Supply with Low Noise
Model: Modular Online UPS Power Melody Star Series (3ph in/3ph out)
Modular UPS Quick View
1: UPS with 3 Phase 208vac 220Vac or 380Vac 400Vac 415Vac Input and Output
2: UPS with high frequency tech and double conversion design
3: Modular UPS with
4: Strong load adaptability for linear and nonlinear load
5: Modular UPS with pure sine waveform and stable output
Key Features
UPS with Modular design and hot swappable.
Double DSP controller for individual power module.
Strong load adaptability for linear and nonlinear load.
Large touch screen LCD with plenty of information.
IGBT modules rather than discrete components are applied in the power module.
Intelligent module and system protection design.
Independent charger for batteries, intelligent battery management system.
Totally front access, top and bottom cable connection.
Inbuilt power distribution for input and output connection.
Incredible low noise system design.
Digital paralleling technology, very low circle current between modules.
Digital control for the whole parts including rectifier, inverter, charger and discharger.
Each individual module is configured with independent controller, avoid single point failure risk.
MS Series 10K-200Kva |
||||
Capacity |
10-200KVA |
|||
Main Input |
||||
Input voltage |
380V/400V/415V(line to line) |
|||
Input frequency |
50/60Hz |
|||
Power factor |
> 0.99 |
|||
Input cuurent THD(Total Harmonic Distortion) |
< 3% |
|||
Input voltage window |
-40%~+25% |
|||
Frequency window |
40-70HZ |
|||
Battery |
||||
Battery voltage |
± 240VDC |
|||
Charger power |
20%*Power |
|||
Charger voltage precision |
1% |
|||
Bypass |
||||
Bypass voltage |
380V/400V/415V, three phase |
|||
Bypass voltage window |
-20%-+15%, full load, settable |
|||
Bypass overload capabiltiy |
150%, long time operation |
|||
180%, shut down after 10 minutes |
||||
> 180%, shut down after 200ms |
||||
Output |
||||
Output voltage |
380V/400V/415V, three phase |
|||
Voltage precision |
± 0.5% (balance load), ± 1% (unbalance load) |
|||
Voltage THD(Total Harmonic Distortion) |
THD< 1%(linear load), THD< 3%(nonlinear load) |
|||
Power factor |
0.8 |
|||
Phase tolerance |
120° ± 0.5° (balance and unalance load) |
|||
Crest factor |
3: 1 |
|||
Overload capabiltiy |
110%, transfer to bypass after 1hour |
|||
125%, transfer to bypass after 10 minutes |
||||
150%, transfer to bypass after 1 minute |
||||
> 150%, transfer to bypass after 200ms |
||||
System |
||||
System efficiency |
Normal mode: 95% |
|||
ECO mode: 99% |
||||
Battery mode efficiency |
Shenzhen UPSEN Electric Co., Ltd [China (Mainland)]
Business Type:Manufacturer |